Controls and Safety : Automatic Thermostat
  >  
Type Y0A9, Y0A8
Type Y0A9, Y0A8
Type Y0A9, Y0A8
Bulb and capillary thermostat, IP55 plastic enclosure with internal adjustment, and additional internal connection block. One pilot light, 1, 2 or 3 M20 cable glands for round or oblong cables. Also available with outside adjustment knob.
Controls and Safety
Automatic Thermostat
Check PDF
Click to see more languages available in the datasheet
Product applicable fields
  • Air and Fluid heating solutions
  • Renewable energy
  • Industry
  • Ventilation
  • Professionnal kitchen
  • Agriculture and Farming
  • Petrochemistry
  • Fire Systems
product presentation

Applications

Distance temperature control in professional premises where good protection against liquid splashes or dust is requested. Output with 2 or 3 cable glands, allowing direct connection of heat tracing cables, radiators or immersion heaters.

Housing: Reduced height, IP44, black PC-ABS fiberglass reinforced, UL94V0. High impact and UV resistance. 2 removable wall mounting lugs.

Cable input: M20 cable glands. Delivered with 2 or 3 cable glands. Special cable glands for oblong or flat heat tracing cables are available on request. Positioning the cable glands allows variations in the mounting position.

Set point adjustment: By °C printed knob for external adjustment models, by screw driver and printed dial on internal adjustment models. °F values available in option

Sensing element: Liquid filled bulb, distance measurement with capillary.

Temperature adjustment ranges: -35+35°C (-30+95°F), 4-40°C (40-105°F), 30-90°C (85-195°F), 30-110°C (90-230°F),
50-200°C (120-390°F), 50-300°C (120-570°F), 100-400°C (210-750°F), 100-500°C (210-930°F).

Capillary length: 1.5 m

Electrical connections: On screw terminals. (It is possible to connect 2 wires 1.5mm² on each terminal). One main terminal and 3 terminals are available for neutral connection. This allows, for example, connecting two heat trace heaters.

Mounting: Wall mounting, by two side lugs with holes for dia. 4mm screws, 69mm distance.

Pilot light: Neon, 230V, standard in red, parallel connection on the load

Contact: SPNC (open on temperature rise).

Electrical rating, resistive loads:
16A 250V, 50 ~60Hz: >100000 cycles, 20A 250V, 50 ~60Hz: ≥50000 cycles, 10A 400V, 50 ~60Hz: ≥50000 cycles.

Electrical rating, inductive loads:
6A 250V, 50 ~60Hz: >100000 cycles

Minimum Storage temperature: -35°C (-30°F)

Maximum ambient temperature: 60°C (140°F)